Installation Recommendations
Preliminary design
Enclosure placement / Enclosure room
A. Ensure sufficient lighting / illumination at the
installation space.
B. Provide suitable , safe access / staging to elevated
items.
C. Provide auxiliary AC supply together with the
associated AC distribution panel and may be with
motor control unit (MCC) where applicable.
D. Standard tool kit should be available easily and
quickly. It should be protected from corrosion and
stored in a dry place.
E. If spares are supplied alongwith the equipment, they
should be protected from corrosion and stored in a
dry place.
F. In case of multiple enclosures provide minimum 2
meters or sufficient clearance to open adjacent doors
simultaneously of two enclosures.
G. While making the layout, provision should be made
for :
I. Cables
II. Fuel lines
III. Breather vent
IV. Coolant / lube oil drain
V. Oil storage
VI. Spares storage
H. Normally, all entry / exit provisions of above are
considered in enclosure design. Try to avoid additions.
If it is required to have additional entry / exit
provisions, ensure for proper sealing of noise,
temperature and entry/exit of foreign particles.
I. Access and clearance
i. Enough opening / shutters should be provided
so that entry and placement of the enclosure is
easily possible.
ii. Generator sets will require access for service to
both sides of the engine as well as the control/
alternator end of the machine. Local electrical
codes may require specific working space for
electrical equipment. Allow for working space equal
to the width of the genset on both sides and rear.
Also ensure sufficient overhead clearances are
provided.
J. Please refer table for typical acoustic enclosure sizes.
K. Future expansion plans should be considered while
deciding total area.
L. The generator room / area around enclosure should
not be used for storage purposes.
M.Avoid installing the enclosure beside heat generating
equipment, or directly below water or steam pipes or
in the vicinity of corrosive substances or vapours,
metal particles and dust.
Preliminary design
Typical acoustic enclosure dimensions*
Genset Model Prime Rating Engine Model Enclosure Dimensions
(kVA) Length (mm) Width (mm) Height (mm)
C 15 D5 P 15 X 1.7 G1 2200 900 1375
C 20 D5 P 20 X 2.5 G1 2200 900 1375
C 25 D5 P 25 X 2.5 G2 2200 900 1375
C 30 D5 P 30 S 3.8 G2 2800 1150 1450
C 35 D5 P 35 S 3.8 G3 2800 1150 1450
C 40 D5 P 40 S 3.8 G4 2800 1150 1575
C 50 D5 P 50 S 3.8 G6 2800 1150 1575
C 62.5 D5 P 62.5 S 3.8 G7 2950 1150 1575
C 75 D5 P 75 6BT 5.9 G1 3850 1150 1700
C 82.5 D5 P 82.5 6BT 5.9 G1 3850 1150 1700
C 100 D5 P 100 6BTA 5.9 G1-I 4000 1150 1700
C 125 D5 P 125 6BTA 5.9 G2-I 4000 1150 1700
C 140 D5 P 140 6BTAA 5.9 G1-I 4000 1150 1700
C 160 D5 P 160 6CTA 8.3 G1-I 4500 1500 1850
C 180 D5 P 180 6CTA 8.3 G2-I 4500 1500 1850
C 200 D5 P 200 6CTAA 8.3 G1-I 4500 1500 1850
C 250 D5 P 250 6CTAA 8.3 G4 4850 1700 2050
C 320 D5 P 320 NTA 855G2-I 5500 2000 2450
C 380 D5 P 380 NTA 14 G3 5500 2000 2450
C 500 D5 P 500 KTA 19 G9 6500 2000 2300
C 600 D5 P 600 VTA28 G3-I 7000 2500 2925
C 625 D5 P 625 VTA28 G5-I 7000 2500 2925
C 750 D5 P 750 KTA 38 G2-I 7500 2500 2925
C 800 D5 P 800 KTA 38 G3-I 7500 2500 2925
* Dimensions of the enclosure are excluding the silencer.